A temperature transmitter is commonly used to convert the output signal from temperature sensors like RTDs (Resistance Temperature Detectors) or thermocouples into a standard 4–20 mA current signal that can be read by a PLC or control system. This process helps ensure accurate temperature measurement over long distances while minimizing signal loss or noise interference.
In this article, we explain how to properly connect an RTD or thermocouple to a temperature transmitter and then interface that transmitter with a PLC. The configuration may vary based on the type of transmitter used – whether it's a single-channel, dual-channel, or multi-point temperature transmitter.
We will use examples such as the Rosemount temperature transmitter and the ABB temperature transmitter to demonstrate basic wiring practices and connection tips. Each transmitter model may have specific requirements, such as:
An RTD temperature transmitter is an electronic device that converts the low-level resistance signal from an RTD (Resistance Temperature Detector) into a standardized 4–20 mA current output. This signal can then be transmitted over long distances to a PLC, DCS, or monitoring instrument using simple copper wiring.
The transmitter typically supports 2-wire or 3-wire RTD inputs, such as the PT100 RTD with alpha = 0.00385. It generates a 4 mA current at the low end of the selected temperature range and 20 mA at the high end. This proportional output makes signal processing and control integration easy and standardized.
Most industrial RTD transmitters, including those from vendors like Rosemount, ABB, Siemens, Yokogawa, and Endress+Hauser, are powered by an external unregulated DC power supply. The transmitter is often installed inside a temperature sensor head to minimize signal noise and protect the internal electronics.
Note: Standard RTD transmitters do not provide isolation between their input terminals and the 4–20 mA output. This means proper grounding and shielding practices are important for noise immunity.
Wiring RTDs to a temperature transmitter depends on the type of RTD sensor used. RTD transmitters are designed to accept 2-wire or 3-wire configurations, and the wiring setup must match accordingly to ensure accurate temperature measurement.
In a 2-wire system, both the excitation and sensing occur through the same pair of wires. A jumper is often installed internally or externally on the transmitter to compensate for the lead wire resistance. This type of connection is simple but less accurate than 3-wire configurations due to lead resistance errors.
The 3-wire RTD connection is commonly used in industrial applications. It helps eliminate the error caused by wire resistance by using one lead wire as a reference. The three wires are connected to the +IN, –IN, and COM terminals of the transmitter, depending on the vendor.
For both configurations, connect the DC power supply in series with the load and the transmitter across the (+PS) and (–PS) terminals. The RTD sensor wires are connected to the (+IN) and (–IN) terminals. The current output (4–20 mA) travels through the loop to the monitoring device or PLC input card.
RTD temperature transmitters require periodic calibration to ensure accurate temperature-to-current signal conversion. The calibration process involves adjusting the transmitter’s Zero (Z) and Span (S) potentiometers to produce exactly 4 mA and 20 mA current outputs for specified resistance (ohmic) inputs that correspond to the temperature range.
Before starting, ensure you have the following:
Connect the transmitter to the calibration setup as shown in the wiring diagram. Use standard copper test leads for accurate resistance injection.
You may also use a temperature simulator to inject simulated RTD signals rather than ohmic values, as long as the calibration point values match the transmitter’s range.
Tip: This calibration process is valid for most industrial RTD transmitters from ABB, Rosemount, Siemens, and Yokogawa. Always refer to vendor-specific manuals for model-based resistance-to-temperature mappings.
Temperature transmitters may sometimes malfunction or produce incorrect readings. The following troubleshooting steps can help identify and resolve common issues related to wiring, power supply, and load resistance.
Loop Resistance (max) = (Vsupply – 8V) ÷ 0.020A
Example: For a 24V power supply:
Loop Resistance = (24V – 8V) ÷ 0.020A = 800 Ω
Required Current = 5 × 28 mA = 140 mA minimum
If the issue persists after following these steps, consult the transmitter’s user manual or contact technical support for further assistance.
A Thermocouple Temperature Transmitter is a two-wire signal conditioning device designed to accept low-level millivolt signals from thermocouple sensors and convert them into a standardized 4–20 mA current output. This output is linearly proportional to the temperature measured by the thermocouple.
Since thermocouples generate very small millivolt signals (in the range of ±50 mV), these transmitters are essential for boosting the signal and transmitting it over long distances without significant loss or interference. The current signal can be easily sent over standard copper wires to PLCs, DCS systems, or remote indicators.
The transmitter typically supports multiple thermocouple types such as:
The output current begins at 4 mA for the lowest point in the configured temperature range and linearly rises to 20 mA at the highest point of the range. This allows easy integration with standard analog input modules and display instruments.
Thermocouple transmitters are commonly mounted in field enclosures, connection heads, or DIN rails, providing reliable and noise-resistant analog signal transmission for process control and monitoring.
A Thermocouple Temperature Transmitter is a two-wire, loop-powered device that accepts low-level millivolt signals from thermocouples and converts them into a standardized 4–20 mA analog output signal. This signal is directly proportional to the temperature measured by the thermocouple.
Because thermocouples generate very small voltages (typically in millivolts), they are not ideal for direct transmission over long distances due to noise and signal loss. A thermocouple transmitter solves this by amplifying and converting the signal into a robust 4–20 mA signal that can be transmitted using standard copper cables.
Most transmitters support common thermocouple types such as:
The transmitter outputs 4 mA at the low end of the configured temperature range and 20 mA at the high end. This proportional output allows integration with PLCs, DCS systems, or temperature indicators.
Wiring typically involves connecting the thermocouple sensor to the input terminals of the transmitter, and connecting the loop power supply and receiving device (e.g., PLC analog input) in series with the output terminals. Refer to the manufacturer's manual for polarity and grounding instructions.
Wiring a thermocouple temperature transmitter involves two major connections: the power loop and the sensor input terminals. A standard 2-wire temperature transmitter uses the same pair of wires for both power and signal transmission (4–20 mA).
Connect a regulated DC power supply in series with the load (e.g., PLC analog input, DCS, or indicator) to the transmitter's power terminals:
The current loop must complete the circuit by returning to the negative terminal of the power supply. The load device (monitoring instrument) can be placed on either side of the power leads depending on your system design.
Connect the thermocouple wires to the input terminals of the transmitter as follows:
Always ensure that the polarity of the thermocouple leads matches the input terminal labeling to avoid reverse signal issues. Use correct thermocouple extension wires (matching type) for accuracy.
To ensure accurate calibration, a stable 0°C reference is often used via an ice bath:
Make sure the thermocouple wire type matches the calibration type of the transmitter (e.g., Type K, J, T, or E). Double-check polarity of the input connections. If using a simulator or calibrator, refer to the transmitter’s manual for correct zero and span values.
Use precision calibration tools like a thermocouple simulator (e.g., Model CL511) for better accuracy. Always allow the system to stabilize for a few seconds before recording readings.
Incorrect operation or malfunction of a thermocouple temperature transmitter may result from several common wiring or configuration issues. Follow the steps below to systematically diagnose and resolve the issue.
A reversed polarity connection can result in abnormal readings, such as a drop in current when temperature increases. Check the following connections using the transmitter wiring diagram (e.g., Figure 2-6):
Loose or damaged wiring can cause unstable or intermittent operation.
Too much resistance in the current loop or an underpowered power supply can result in reduced or unstable transmitter output.
Use this formula to determine the maximum loop resistance the system can tolerate:
Loop Resistance (max) = (Vsupply – 7V) / 0.020 A
Example: For a 24V DC supply,
Loop Resistance = (24V – 7V) / 0.020 A = 17V / 0.020 A = 850 ohms
Ensure your power supply can handle the total current draw:
An RTD/Thermocouple Signal Transmitter is a temperature signal conditioning device designed to work with both types of temperature sensors — RTDs and thermocouples. It receives the low-level signal from the sensor (millivolts for thermocouples or ohms for RTDs), processes it, and converts it into a standardized output such as 4–20 mA or digital communication (e.g., HART).
This type of transmitter helps eliminate signal loss, improves noise immunity, and simplifies the connection to automation systems like PLCs, DCS, or SCADA. Depending on the model, it can be single-channel or multi-channel and is available in head-mount, rail-mount, or field-mount formats.
Here are some commonly used signal transmitters that support both RTD and thermocouple inputs. These models are widely used in industrial temperature measurement applications:
An RTD (Resistance Temperature Detector) sensor typically uses a 3-wire configuration to minimize the effect of lead wire resistance. The RTD is connected to a temperature transmitter which converts the resistance signal into a standard 4–20 mA output signal. This analog signal is then fed into the PLC’s analog input module.
A thermocouple (such as K-type) generates a millivolt signal based on temperature difference between its two junctions. This small signal is processed by a temperature transmitter which converts it into a robust 4–20 mA signal. The transmitter is then connected to a PLC analog input for monitoring and control.
Example transmitter: Siemens SITRANS T (supports thermocouple input including K-type)